panelboards, switchgear, switchboards,   the system with narrow or no margin   increase available short-circuit currents
            and service entrance equipment, they   may be quite expensive. We can’t   seen in the power distribution system.
            will be there for a very long time and   say that the NEC® didn’t warn us.  Changing impedance contributors in
            will face changes that will place more or                            the system, such as transformers, can
            less demands on the power distribution                               have significant impact to the available
            system. We arrive at the size of such                                short-circuit current. We use calculated
            equipment as services, conductors,   SHORT-CIRCUIT                   short-circuit currents when we select
            and transformers based upon our load   CALCULATIONS                  such equipment as circuit breakers,
            calculations found in Article 220. A quick                           fuses, and other types of electrical
            glance at Section 220.12, titled “Lighting   A short-circuit calculation considers   distribution equipment. Short-circuit
            Load for Specified Occupancies,” shows   the impedances of a system as well   current ratings (SCCR) and interrupting
            us an informational note that says, “The   as all fault contributors. Popular key   ratings are two very important parameters
            unit values are based on minimum load   contributors to short-circuit current   that come to mind that are directly
            conditions and 100 percent power factor   include the utility feed, motors, and   compared with the available short-
            and may not provide sufficient capacity   generators on site. Popular reducers of   circuit current at the point of application.
            for the installation contemplated.”   short-circuit current include conductors,   Equipment selected with SCCR and
            Once we have selected conductors and   transformers, inductors, and busway.   interrupting ratings that are very close
            transformers and electrical equipment   Changes in the power distribution system   to the calculated available short-circuit
            and have them installed, expanding   can impact the available short-circuit   current do not provide for addition of
            capacity when we have designed                                       motors or replaced transformers.